3. ACON-C/CG, PCON-C/CG
CC-Link
17
3.6 Communication Speed Setting
The communication speed is set using the parameters.
Set the parameter No. 86 “FBRS: Filed Bus Communication Speed” using the RC personal computer
application software.
(Refer to “3.10 CC-Link Related Parameters”).
Set Value Communication Speed
0: (Already set in system delivery) 156kbps
1 625kbps
2 2.5Mbps
3 5Mbps
4 10Mbps
* Entering any value except for the ones described above will
cause an “Excessive Input Value Error”.
Note: After the parameter setting, turn on the power to the controller again and return the mode toggle switch on the front
of the controller to “AUTO” side.
When the switch is set to “MANU”, the operation using PLC is not available.