Part 1 Installation
2. Safety Circuit for PX Type (Standard Specification) Controller
The PX type controller has a built-in drive source cutoff circuit just like IAI’s other controllers.
The drive source cutoff circuit consists of a relay and conforms to safety category B. If your equipment
must meet a higher safety category, use the QX type (global specification) controller explained later.
Connect the control power supply and motor power supply to the same power source and also turn on/off
the control power supply and motor power supply at the same time.
The teaching pendant port can be connected to either an IAI’s standard teaching pendant or ANSI
teaching pendant. Note, however, that redundant safety circuits cannot be configured even if an ANSI
teaching pendant is used.
Set the teaching pendant type switch located above the teaching pendant connector to the position
appropriate for the teaching pendant used. Set the switch to the left for an ANSI teaching pendant, or to
the right for IAI’s standard teaching pendant.
Note: If the teaching pendant type switch is not set properly, the safety gate switch will not function.
The emergency stop line and enabling line are driven by the controller’s internal power supply. It should
be noted that the safety circuit cannot be driven by an external power source.
Do not use the internal power supply provided for the system I/O connector, for any other purpose. It may
damage the equipment or cause it to malfunction.
The tables below list the signals and wiring methods of the safety circuit interface connector.
System I/O Connector for PX Type
Item Overview Details
COMBICON (2-row, 9-pin) MCD1.5/9-G1-3.5P26THR (by Phoenix Contact)
Cable end connector FMC1.5/9-ST-3.5
Connector
Applicable cable size 0.2 to 1.3 mm
2
(AWG24-16)
Terminal Assignments
Pin
No.
Signal
name
Overview Details
9 DET IN Not connected Not used
8 IN To external EMG Emergency-stop detection input
7
EMGin
+24 V
24 V power output for emergency-stop
detection input
6 line+
Shorted
Wired before shipment
5
EMG1
line- To external EMG
Emergency stop switch 1
Wire circuit 1 connected to EMG of the TP
4 line+ Not connected
3
EMG2
line- Not connected
Not used
2 Out+ Not connected
Left
1
SDN
Out- Not connected
External relay drive cutoff contact outputs
18 DET +24 V Not connected Not used
17 IN To external ENB Enable detection input
16
ENBin
+24 V 24 V power output for enable detection input
15 line+
Shorted
Wired before shipment
14
ENB1
line- To external ENB
Enable switch 1 (safety gate, etc.)
Wire circuit 1 connected to ENB of the TP
13 line+ Not connected
12
ENB2
line- Not connected
Not used
11 Out+
Right
10
RDY
Out-
May be used if
necessary
Ready signal contact outputs (dry contacts)
(for inductive load of up to 400 mA)